3.6kV Vacuum Contactor 3200A
Hai Bang Medium Voltage& Low Voltage Vacuum Contactors – Type JCZ3-3.6D/D-3200A are suitable for AC 50~60Hz power systems, main circuit rated voltage 1.14kV-3.6kV, and rated current 3200A. This type of 3200A Vacuum Contactor is used to directly or remotely connect and disconnect the main circuit and frequently control AC motors, transformers and other electrical control occasions. 3.6kV Vacuum Contactor 3200A is widely used in petroleum, coal mine explosion-proof equipment and other occasions. The altitude of the environment where the Vacuum Contactor is used does not exceed 1000 meters above sea level.
We have other types of 3.6kV Medium Voltage Vacuum Contactor, whose rated current are 160A, 250A, 400A, 630A (JCZ3-3.6D/D-160~630A) and 800~2500A (JCZ3-3.6D/D-800~2500A). Please refer to the categories for more information.
Types:
JCZ3-3.6D/D-3200A
Technical Data:
Name |
Unit |
Value | ||
Main circuit |
Rated working voltage (Ue) |
kV |
1.14kV-3.6kV |
|
Rated working current (Ie) |
A |
3200A | ||
Rated frequency (fr) |
Hz |
50~60 | ||
Rated connecting capacity |
kA |
12.5 | ||
Rated breaking capacity |
kA |
10 | ||
Ultimate breaking capacity |
kA |
12.5 | ||
Rated short time withstand current |
kA |
10 | ||
Rated peak withstand current |
kA |
12.5 | ||
Rated short circuit duration |
s |
4 | ||
Power frequency withstand voltage |
Wiring terminal to earth |
kV |
18 |
|
Vacuum breaks |
kV |
18 | ||
Lightening impulse withstand voltage |
kV |
40 | ||
Control circuit |
Rated voltage (Us) |
V |
AC 110/220/380 |
|
DC 110/220 | ||||
Rated power (Ps)electric holding(800~3200A) |
VA |
≤600/50 (absorbing/holding) | ||
Rated power (Ps) mechanical holding(800~2500) |
VA |
≤900/600 (Closing/opening) | ||
Auxiliary circuit |
Form |
(3a+2b) |
||
Rated value | AC 380V/5A, | |||
DC 380V/1A | ||||
Control circuit, auxiliary circuit to earth power frequency withstand voltage |
kV |
2 | ||
Rated operating frequency |
Long-term |
time/h |
300 |
|
Short-term |
time/h |
600 | ||
Mechanical endurance |
10000 times |
10 | ||
Electrical endurance |
10000 times |
10 | ||
Mechanical characteristics |
Closing time |
ms |
≤200 |
|
3-phase asynchronous time |
ms |
≤3 | ||
Original opening time |
ms |
≤150 | ||
Closing tripping |
ms |
≤10 |
Remark:
1. Rated control voltage can be made according to customer’s requirements.
2. For the mechanical holding type, the locking device needs to be replaced every 100,000 times.