1.14kV 800A Vacuum Contactor - low Voltage Vacuum Contactor, rated voltage 1.14kV, rated current 630-800A

General Description:

Hai Bang low Voltage Vacuum Contactor – Type CKJ3-1.14D/D-630~800 is applicable on AC 50-60Hz power systems, rated voltage 1140V, rated current 630-800A. This type of 1.14kV vacuum contactor is used to directly or remotely connect and disconnect the main circuit and frequently control AC motors, transformers and other electrical control occasions. Haibang 1.14kV 800A Vacuum Contactor is widely used in petroleum, coal mine explosion-proof equipment and other occasions. The altitude of the environment where the 1.14kV Vacuum Contactor is used does not exceed 1000 meters above sea level.

Please refer to the categories for other types of 1.14kV Vacuum Contactors with other values of rated current.

Technical Data:

Name Unit Value
Main circuit Rated working voltage (Ue) V 1140
Rated working current (Ie) A 630, 800
Rated frequency (fr) Hz 50~60
Rated connecting capacity A 10Ie (AC-4)
Rated breaking capacity A 8Ie (AC-4)
Rated short circuit duration s 4
Ultimate breaking capacity kA, time 6.3kA/3times
Power frequency withstand voltage Wiring terminal to earth kV 4.2
Vacuum breaks kV 10
Lightening impulse withstand voltage kV 8
Control circuit Rated voltage (Us) V AC 110/220/380
DC 110/220
Rated power (Ps) electric holding VA ≤900/50 (absorbing/holding)
Auxiliary circuit Form (3a+2b)
Rated value AC 380V/5A,
DC 380V/1A
Control circuit, auxiliary circuit to earth power frequency withstand voltage kV 2
Rated operating frequency Long-term time/h 600(AC-3), 300(AC-4)
Short-term time/h 2000
Mechanical endurance 10000 times 100
Electrical endurance 10000 times 60(AC-3), 6(AC-4)
Mechanical characteristics Closing time ms ≤200
3-phase asynchronous time ms ≤3
Original opening time ms ≤150(electric holding)
Closing tripping ms ≤10

Remark: 1. rated control voltage can be made according to customer’s requirements.

2. Can be used for 2000V.

Inquiry Cart 0