Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd

Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd

Manufacturer from China
Verified Supplier
2 Years
Home / Products / 3 Phase Vacuum Contactor /

12kV Vacuum Contactor For Capacitor - High Voltage Vacuum Contactor

Contact Now
Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd
Visit Website
City:wuxi
Province/State:jiangsu
Country/Region:china
Contact Person:MrMinjie
Contact Now

12kV Vacuum Contactor For Capacitor - High Voltage Vacuum Contactor

Ask Latest Price
Video Channel
Brand Name :haibang
Place of Origin :china
MOQ :1
Contact Now

Add to Cart

Find Similar Videos
View Product Description

12kV vacuum contactor for Capacitor - High Voltage Vacuum Contactor, rated voltage 12 kV, rated current 160A, 250A, 400A, 630A

General Description:

Hai Bang high voltage 3 phase Vacuum Contactor – Type JCZ5 12kV vacuum contactor for Capacitor is applicable on AC 50-60 Hz power systems, rated voltage up to 12kV, rated current up to 630A. This type of 12kV vacuum contactor for Capacitor is used to directly or remotely connect and disconnect the main circuit and frequently control capacitive loads, AC motors, transformers and other electrical equipment. JCZ5 12kV vacuum contactor for Capacitor is widely used in power grid reactive power compensation, chemical industry, metallurgy, water supply and drainage treatment, underground coal mine equipment and other occasions. The altitude of the environment where the 3 phase vacuum contactor is used does not exceed 1000 meters above sea level.

Types:

JCZ5-12J/D-160-1.6

JCZ5-12J/D-250-2.5

JCZ5-12J/D-400-4.0

JCZ5-12J/D-630-6.3

Technical Data:

Name Unit Value
Main circuit Rated working voltage (Ue) kV 12kV
Rated working current (Ie) A 160A~630A
Rated frequency (fr) Hz 50~60
Rated connecting capacity A 10Ie (AC-4)
Rated breaking capacity A 8Ie (AC-4)
Rated short time withstand current A 10Ie
Rated peak withstand current A 25Ie
Rated short circuit duration s 4
Ultimate breaking capacity 6.3 kA , 3 次
Power frequency withstand voltage Wiring terminal to earth kV 42
Vacuum breaks kV 42
Lightening impulse withstand voltage kV 75
Rated single capacitor breaking current (C2) A 160-400
Control circuit Rated voltage (Us) V AC or DC. 110/220
Rated power (Ps)electric holding VA ≤1000/100 (absorbing/holding)
Auxiliary circuit Form (3a+2b)~(6a+5b)
Rated value AC 380V/5A,
DC 380V/1A
Control circuit, auxiliary circuit to earth power frequency withstand voltage kV 2
Rated operating frequency Long-term time/h 300
Short-term time/h 600
Mechanical endurance 10000 times 100
Electrical endurance 10000 times 25(AC-3), 10(AC-4)
Mechanical characteristics Closing time ms ≤200
3-phase asynchronous time ms ≤3
Original opening time ms ≤160
Closing tripping ms ≤10

Remark: 1. rated control voltage can be made according to customer’s requirements.

2. For the mechanical holding type, the locking device needs to be replaced every 100,000 times.

Inquiry Cart 0