Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd

Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd

Manufacturer from China
Verified Supplier
2 Years
Home / Products / Medium Voltage Vacuum Contactor /

3.6kV 1600A Vacuum Contactor - Medium Voltage Vacuum Contactor

Contact Now
Wuxi Haibang Mechanical & Electrical Manufacturing Co.,Ltd
Visit Website
City:wuxi
Province/State:jiangsu
Country/Region:china
Contact Person:MrMinjie
Contact Now

3.6kV 1600A Vacuum Contactor - Medium Voltage Vacuum Contactor

Ask Latest Price
Video Channel
Brand Name :haibang
MOQ :1
Contact Now

Add to Cart

Find Similar Videos
View Product Description

3.6kV 1600A Vacuum Contactor - Medium Voltage Vacuum Contactor, rated voltage 3.6kV, rated current 800A, 1000A, 1250A, 1600A, 2000A, 2500A

General Description:

Hai Bang 3.6kV heavy current Vacuum Contactor – Type JCZ3-3.6D/D-800~2500A is suitable for AC 50~60Hz power systems, main circuit rated voltage 3.6kV, and rated current 800A, 1000A, 1250A, 1600A, 2000A, 2500A. JCZ3 3.6kV Medium Voltage Vacuum Contactor is widely used in petroleum, coal mine explosion-proof equipment and other occasions. Hai Bang 3.6kV Vacuum Contactor is used to directly or remotely connect and disconnect the main circuit and frequently control AC motors, transformers and other electrical control occasions. The altitude of the environment where the 3.6kV medium voltage Vacuum Contactor is used does not exceed 1000 meters above sea level.

We have other types of 3.6kV Medium Voltage Vacuum Contactor, whose rated current are 160A, 250A, 400A, 630A (JCZ3-3.6D/D-160~630A) and 3200A (JCZ3-3.6D/D-3200A). Please refer to the categories for more information.

Types:

JCZ3-3.6D/D-800~2500A

Technical Data:

Name Unit Value
Main circuit Rated working voltage (Ue) kV 3.6kV
Rated working current (Ie) A 800A, 1000A, 1250A, 1600A, 2000A, 2500A
Rated frequency (fr) Hz 50~60
Rated connecting capacity kA 12.5
Rated breaking capacity kA 10
Ultimate breaking capacity kA 12.5
Rated short time withstand current kA 10
Rated peak withstand current kA 12.5
Rated short circuit duration s 4
Power frequency withstand voltage Wiring terminal to earth kV 18
Vacuum breaks kV 18
Lightening impulse withstand voltage kV 40
Control circuit Rated voltage (Us) V AC 110/220/380
DC 110/220
Rated power (Ps) electric holding(800~3200A) VA ≤600/50 (absorbing/holding)
Rated power (Ps) mechanical holding(800~2500) VA ≤900/600 (Closing/opening)
Auxiliary circuit Form (3a+2b)
Rated value AC 380V/5A,
DC 380V/1A
Control circuit, auxiliary circuit to earth power frequency withstand voltage kV 2
Rated operating frequency Long-term time/h 300
Short-term time/h 600
Mechanical endurance 10000 times 10
Electrical endurance 10000 times 10
Mechanical characteristics Closing time ms ≤200
3-phase asynchronous time ms ≤3
Original opening time ms ≤150
Closing tripping ms ≤10

Remark: 1. rated control voltage can be made according to customer’s requirements.

2. For the mechanical holding type, the locking device needs to be replaced every 100,000 times.

Inquiry Cart 0